Sdc 1581S MINI EXIT CHECK DELAYED EGRESS EMLOCK User Manual

Browse online or download User Manual for For Home Sdc 1581S MINI EXIT CHECK DELAYED EGRESS EMLOCK. SDC 1581S MINI EXIT CHECK DELAYED EGRESS EMLOCK User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 10
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
SECURITY DOOR CONTROLS
801 Avenida Acaso, Camarillo, Ca. 93012 • (805) 494-0622 • Fax: (805) 494-8861
www.sdcsecurity.com • E-mail: service@sdcsecurity.com
P:\INSTALLATION INST\Delayed Egress\INST-1581S\INST-1581S.vsd REV D7 03-13 Page 1
INSTALLATION INSTRUCTIONS
MINI EXIT CHECK
®
DELAYED EGRESS EMLOCK
®
1581S
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15 SECONDS.
California Building
Code Compliant
KEEP PUSHING. THIS DOOR
WILL OPEN IN 15 SECONDS.
ALARM WILL SOUND.
Application
When unauthorized egress is initiated, the Exit Check
®
delays egress through the door for a period of 15 seconds.
Meanwhile, the person exiting must wait allowing personnel or security respond. The door unlocks after the 15 second
delay period has elapsed, permitting egress. A signal from the fire/life safety system will release the lock immediately
for uninhibited egress in an emergency.
Exit Check
®
applications include:
Restricting the egress of patients for their own safety.
Restricting the egress of commercial center patrons for minimum security application needs.
Standard Features
Small & Compact Size
650 lbs. Holding Force
15 Second Exit Delay when activated.
1 Second Nuisance Delay
Subdued Alarm with 2 Distinct Tones:
- Alarm Activation Intermittent
- Door Release – Continuous
Choice of Activation Trigger:
- Door Movement
- Exit Device w/ REX Switch
- Touch Sense Bar w/REX Switch
Instant Reset from Bypass mode for interfacing
with Patient Monitoring Systems.
Vandal resistant Proximity Sensor Trigger
Auto Sensing 12/24VDC input power
Low Power Consumption
5 foot Power Cable
Connection for Tandem Option (Pairs of Doors)
Optional Features
30 Second Exit Delay
DPS Door Position Switch
BAS Bond Alert Sensor (Internal)
Tandem / Slave Cable
3' Cable – 1581S-TC3
10' Cable – 1581S-TC10
Building & Fire Life Safety Code Compliant
1581SND,NA,NH,NC
IBC International Building Code
IFC International Fire Code
NFPA 101 Life Safety Code
NFPA 1, UFC, Uniform Fire Code
UBC Uniform Building Code
CBC California Building Code
SBC Standard Building Code
1581SBD,BH,BC
BOCA National Building Code compliant
Chicago Building Code compliant
Selectable Automatic & Manual Power-Up
Auto Power-Up – Occurs when power is restored and/or
the fire panel is restored (Not available on California
Versions).
Manual Power-Up – This is a UBC & California Building
Code Compliant Feature – Only after power restoration
and fire panel reset may the lock be reset manually at the
opening. A power-up key switch or keypad is required
adjacent to the door.
GWXT/GWXT7 Auxiliary Locks
FWAX Special Locking Arrangements
California State
Fire Marshal Listed
CSFM #3774-0324:103
LISTED
CANADA
LISTED
USA
Only the 1581S and the 1581T have been UL listed as “Special Locking
Arrangements” to UL standard 294 and NFPA 101.
Page view 0
1 2 3 4 5 6 7 8 9 10

Summary of Contents

Page 1 - SECURITY DOOR CONTROLS

SECURITY DOOR CONTROLS801 Avenida Acaso, Camarillo, Ca. 93012 • (805) 494-0622 • Fax: (805) 494-8861www.sdcsecurity.com • E-mail: service@sdcse

Page 2 - (NFPA-101)

Sense Bar Trigger Non-LatchingPSB560, MSB550PowerPT-2PT-3Wall Mount Reset StationRequired with 1581SND728918728L702RU101-1AKPowerLatch Monitoring Stri

Page 3 - Digital Entry

P:\INSTALLATION INST\Delayed Egress\INST-1581S\INST-1581S.vsd REV D7 03-13 Page 21581S Operational DescriptionThe door is closed and sec

Page 4 - INSTRUCTION SHEET

Included in PackageARMATURE SCREW PACK1580S-101-C728USingle station two function key switch control for alarm reset and access or sustained bypass.101

Page 5 - DOOR STOP.)

NOTES: - #10 self drill/tap screws provided for up to ⅛" thick metal applications- For applications with heavier gauge material, drill (#21) and

Page 6 - WARNING:

STEP 1. Mount armature to door. (See figures 2A, 2B & 2C.)STEP 2. Install the mounting plate (filler plate and/or angle bracket if needed – see

Page 7 - System Wiring – Pair of Doors

REDBLKGRNBLUBRNWHTORGYELREDBLKGRNBLUBRNWHTORGYELPOWER -POWER +COMNONCCOMNONC600 Series Power Supply1581S Mini Delayed Egress Locking MagnetPSB560 Requ

Page 8 - ROCKER SWITCH SETTINGS

REDBLKGRNBLUBRNWHTORGYELREDBLKGRNBLUBRNWHTORGYELPOWER -POWER +COMNONCCOMNONC+-1581S Mini Delayed Egress Magnet(Set mode switch to SLAVE)PSB560 Request

Page 9

WIRING DETAILS & FUNCTIONS (ALL OPTIONS SHOWN) ROCKER SWITCH SETTINGS1 REX TIME 1 SECOND 10 SECONDS INTERNAL RELOCK TIME DELAY WHEN US

Page 10

STEP 1. After the lock has been mounted to the door and frame per the provided template, make all wiring connections to the lock. At a minimum, thi

Comments to this Manuals

No comments